Are you finding it hard to get the heat to come through?
A fairly common problem is that it is difficult to distribute the heat evenly throughout the property, or that certain parts of the property are warmer or colder.
Does this sound familiar?
These are the times when you raise the flow temperature, increase the speed of the circulation pump and adjust the valves and thermostats.
So what’s happening then?
Unfortunately, this does not solve the problem; instead, it can lead to a higher return temperature, poorer cooling and an imbalance in the system.
What should you do instead?
- Start by checking that you have the correct system pressure and pre-pressure in the expansion vessel.
- The next step is to carry out a reference measurement of the sensors to ensure that they are providing the correct reading, that they are correctly positioned and that they are in good working order.
- If you have district heating, check that the control valve opens and closes as it should.
- Now check the heat transfer in the heat exchanger and make sure the circulation pump is working properly.
Get in touch and we’ll help you analyse the situation and suggest a course of action!